Hygiene Plan 8
Technical details
Product sheet
Specification text
The Hygiene Plan 8 is a decorative radiator with a flat front, without convection fins and without upper grille and side panels, for each project where hygiene is of great importance. With its flat front, the radiator has a timeless design. Furthermore you have, thanks to the 4 side- and 4 bottom connections, a variety of connection possibilities. In addition, it offers a uniform wall distance of 65 mm for types 20 and 30 at the centre connection.
The thermostatic valve insert is factory-set in relation to the size of the radiator. This presetting ensures optimum throughput in the radiator. Factory setting for two-pipe systems, also suitable for one-pipe systems (as long as the valve insert is adjusted to position 8).
Heat output & dimensions
Type overview
Type 10 | Type 20 | Type 30 | |
---|---|---|---|
Height: 300mm | |||
Centre distance: 250mm | |||
W | 301 | 531 | 798 |
kg | 8,44 | 14,64 | 22,00 |
l | 1,84 | 3,29 | 5,20 |
m² | 0,68 | 1,37 | 2,04 |
n | 1,2664 | 1,2988 | 1,3179 |
Height: 400mm | |||
Centre distance: 350mm | |||
W | 394 | 680 | 983 |
kg | 10,79 | 19,26 | 28,53 |
l | 2,35 | 4,49 | 6,57 |
m² | 0,91 | 1,83 | 2,73 |
n | 1,2661 | 1,3021 | 1,3010 |
Height: 500mm | |||
Centre distance: 450mm | |||
W | 481 | 820 | 1168 |
kg | 13,15 | 23,88 | 35,07 |
l | 2,85 | 5,70 | 7,93 |
m² | 1,14 | 2,28 | 3,42 |
n | 1,2657 | 1,3053 | 1,2840 |
Height: 600mm | |||
Centre distance: 550mm | |||
W | 562 | 952 | 1357 |
kg | 15,50 | 28,50 | 41,60 |
l | 3,35 | 6,90 | 9,30 |
m² | 1,37 | 2,74 | 4,11 |
n | 1,2654 | 1,3086 | 1,2671 |
Height: 700mm | |||
Centre distance: 650mm | |||
W | 636 | 1077 | 1550 |
kg | 18,15 | 33,33 | 48,10 |
l | 3,83 | 7,57 | 10,77 |
m² | 1,60 | 3,20 | 4,79 |
n | 1,2654 | 1,3156 | 1,2884 |
Height: 900mm | |||
Centre distance: 850mm | |||
W | 765 | 1308 | 1959 |
kg | 23,45 | 43,00 | 61,10 |
l | 4,80 | 8,90 | 13,70 |
m² | 2,06 | 4,12 | 6,18 |
n | 1,2658 | 1,3295 | 1,3311 |
Calculation Factor per meter length radiator at 75/65/20 °C in accordance with EN442
Characteristic equation: ф = KM x ΔTn
Connections
When mounting as a valve radiator
When mounting as a compact radiator
- the valve insert must be removed.
* = a reduction in heat output will occur when combining low temperature heating with a high temperature difference between inlet and outlet.
Lugs
Type 10
L | A |
500-1100 | 167 |
1200-1600 | 267 |
L | A |
1800-2400 | 267 |
Mounting and connection dimensions
Mounting
Type 10
Type 20
Type 30
* Centre connection only
Connection dimensions
L = Length of the radiator