ECO Galva
Technical details
Specification text
The ECO radiator and its serial flow technology are perfectly suited to operate in low-temperature heating systems. This technology (water flows first through the front panel) results in higher energy efficiency, maximum radiation, faster heating rate and less waste of energy through the back wall. In addition, the ECO Galva radiator is treated with a protective galvanized coating, so it can be used without any concerns in wet areas.
The thermostatic valve insert is factory-set in relation to the size of the radiator. This presetting ensures optimum throughput in the radiator. Factory setting for two-pipe systems, also suitable for one-pipe systems (as long as the valve insert is adjusted to position 8).
Heat output & dimensions
Type overview
Type 11 | Type 21 | Type 22 | Type 33 | |
---|---|---|---|---|
Height: 300mm | ||||
W | 517 | 770 | 958 | 1.349 |
kg | 8,38 | 13,85 | 15,50 | 22,90 |
l | 1,89 | 3,8 | 3,7 | 5,2 |
m² | 2,09 | 2,44 | 3,51 | 5,26 |
n | 1,3145 | 1,2546 | 1,2753 | 1,2716 |
Height: 400mm | ||||
W | 687 | 978 | 1.212 | 1.726 |
kg | 11,68 | 18,28 | 20,55 | 30,53 |
l | 2,34 | 4,8 | 4,77 | 6,8 |
m² | 2,95 | 3,37 | 4,92 | 7,38 |
n | 1,3057 | 1,2729 | 1,2867 | 1,2838 |
Height: 500mm | ||||
W | 848 | 1.174 | 1.452 | 2.071 |
kg | 14,99 | 22,72 | 25,60 | 38,17 |
l | 2,8 | 5,8 | 5,83 | 8,4 |
m² | 3,8 | 4,31 | 6,33 | 9,49 |
n | 1,2968 | 1,2912 | 1,2982 | 1,2959 |
Height: 600mm | ||||
W | 1.000 | 1.360 | 1.679 | 2.387 |
kg | 18,30 | 27,15 | 30,65 | 45,80 |
l | 3,25 | 6,8 | 6,9 | 10 |
m² | 4,66 | 5,24 | 7,74 | 11,61 |
n | 1,2880 | 1,3095 | 1,3096 | 1,3081 |
Height: 700mm | ||||
W | 1.142 | 1.538 | 1.896 | 2.674 |
kg | 22,9 | 32,7 | 38,07 | 57 |
l | 3,77 | 7,57 | 7,63 | 11,25 |
m² | 5,51 | 6,18 | 9,15 | 13,72 |
n | 1,2889 | 1,3152 | 1,3129 | 1,3207 |
Height: 900mm | ||||
W | 1.397 | 1.872 | 2.303 | 3.171 |
kg | 27,40 | 39,65 | 45,60 | 67,94 |
l | 4,8 | 9,1 | 9,1 | 13,75 |
m² | 7,22 | 8,05 | 11,97 | 17,96 |
n | 1,2907 | 1,2751 | 1,2898 | 1,2327 |
Calculation Factor per meter length radiator at 75/65/20 °C in accordance with EN442
Characteristic equation: ф = KM x ΔTn
Connections
Type 11
Type 21 -33
Important notice for ECO radiators: The green ECO air vent is essential for the proper working of the radiator and cannot be replaced by a traditional air vent as the radiator will keep on heating.
Lugs
Length 400-1600
Type 21-33
L | A |
400-1600 | 133 |
Type 11
L | A |
400 | 117 |
500-1600 | 150 |
Length 1800-3000
Type 21-33
L | A |
1800-3000 | 133 |
Type 11
L | A |
1800-2400 | 150 |
Mounting and connection dimensions
Type 11
Type 21
Type 22
Type 33
Type 11
Type 21-33
L = length of the radiator